Ducted AC selection: getting airflow and static pressure right

Build a pressure budget, check the fan operating point and allow for filter loading before selecting a concealed indoor unit.

By Air Solutions
Modern office with finished ceilings and discreet ducted-air outlets

Cooling capacity and airflow are linked, but they are not interchangeable specifications. A concealed indoor unit has to move its required air volume through the installed return path, filters, ducts and terminals. If that system resistance is underestimated, the selected unit may deliver less air than the thermal selection assumes. Increasing the fan setting afterwards is not a substitute for an airside calculation.

At a glance

Select at a stated airflow and external static pressure together. Calculate the controlling air path, confirm the manufacturer’s pressure boundary and check the operating point with both clean and loaded filters.

Start with an air volume, not a pressure setting

Establish the supply airflow needed for the design duty and the intended supply-air condition. Use the selected indoor unit’s performance data to check the corresponding sensible and total cooling. A larger air volume may change coil performance as well as air movement, so it is not automatically an improvement.

Use consistent units in the equipment schedule. For example, 500 L/s is 0.50 m³/s or 1,800 m³/h. Record the intended fan speed or control setting against that airflow. A maximum external-static-pressure figure by itself does not demonstrate that the required airflow is available at that pressure.

Build the pressure budget along the controlling path

Trace the complete air path from return grille to supply terminal. Include relevant external filters, duct friction, bends, transitions, dampers and terminal losses at their actual flows. Parallel branch losses are not all added together: evaluate each path to find the one that determines the fan duty.

Check what the manufacturer includes inside its published unit performance boundary. An internal filter or coil loss already accounted for in that data must not be added again as an external loss. The equipment drawing, fan data and accessory schedule should agree on this boundary.

Further reading: CIBSE Journal: designing ducted air systems and pressure drops

A modest filter allowance can change the selection

The following assumed losses describe one controlling air path at 500 L/s. They are an arithmetic example, not recommended component allowances. Obtain actual losses from the selected components and duct calculation.

Illustrative external pressure budget at 500 L/s
Component on the controlling pathPressure loss
Return grille12 Pa
External filter, clean30 Pa
Return duct and fittings18 Pa
Supply duct and fittings35 Pa
Supply terminal20 Pa
Total, clean filter115 Pa
Additional assumed filter loading15 Pa
Required duty with loaded filter130 Pa

A unit that can provide only 125 Pa at the required airflow would not meet this assumed 130 Pa duty. Even the clean-filter condition must be checked on the applicable fan data; a headline maximum rating is not enough.

Read the fan and system together

The operating point depends on both the fan characteristic and the resistance of the connected system. Check the available fan curves or selection tables at the proposed speed, including the permitted range. An unsuitable inlet arrangement or abrupt outlet connection can also affect installed performance.

If the calculation does not work, review the duct route, filter area, terminal selection and unit choice. Increasing duct area or reducing avoidable fitting losses can be more useful than relying on a higher fan speed. Check acoustic consequences at the same time, including duct breakout, terminal noise and vibration transmission.

Further reading: CIBSE Journal: matching the fan to the ventilation system

Turn the calculation into a commissioning target

Put the design air volume, external pressure duty, filter condition and selected setting on the commissioning sheet. Provide accessible measurement locations and an agreed balancing procedure. Record measured total and terminal airflows rather than accepting the controller’s fan setting as evidence of delivery.

Where results differ, check damper positions, obstructed returns, filter condition, duct leakage and the installed route before revising settings. Keep the final measured values and configuration with the handover records. That baseline makes a future airflow complaint much easier to investigate.