The PEY Series combines a slim ceiling-concealed indoor unit with ducted air distribution for offices, shops and residential interiors. The PEY-ZM18/24/30/36/45JAG-AE range offers R32 inverter cooling from 5.31 to 13.20 kW, with five static-pressure settings to suit a carefully designed duct system.
A compact unit above the ceiling, flexible duct connections and practical operating modes bring cooling into the room while leaving the main equipment out of sight.
Ceiling-concealed installation.
With a unit height of just 250 mm, the PEY-ZM JAG indoor unit is designed for spaces with limited ceiling depth. The unit stays concealed while visible air grilles can be coordinated with the interior. Allowing for suspension, ductwork, drainage and service access completes the installation plan.
Airflow shaped around your space.
Five external static-pressure settings, from 35 to 125 Pa, give the installer flexibility when matching the system to the ductwork. Three fan speeds and a choice of rear or bottom air inlet support different layouts. For rooms where lower noise matters, the catalogue recommends a rear-inlet arrangement.
A drying cycle after cooling.
Internal Dry Mode runs the fan at high speed after cooling or drying operation stops, helping dry moisture on the indoor heat exchanger. Choose a 30- or 60-minute cycle. Drying results depend on indoor temperature and humidity, and the function complements the unit’s normal care routine.
Send your floor plan, room use and any cooling-load assessment. We can compare indoor formats, model combinations and controller options.
Explore the features of the PEY Series and the options available for your system.
250 mm-high concealed unit
All five JAG indoor models share a 250 mm body height and 732 mm depth. Widths range from 900 to 1400 mm. The installer must also allow for ductwork, drainage and maintenance clearances.
Five static-pressure settings
Select 35, 50, 70, 100 or 125 Pa to match a professionally designed duct network. The published specification table uses 50 Pa; the 150 Pa setting belongs to the separate 60-class GAG range.
Three selectable fan speeds
Low, medium and high fan settings provide a choice of airflow. Indoor air volumes and sound-pressure levels for each setting are listed in the model comparison.
Rear or bottom air inlet
The inlet arrangement can be selected to suit the ceiling layout. Rear-inlet installations produce less noise than bottom-inlet arrangements, making them the catalogue’s recommendation for noise-sensitive rooms.
Internal Dry Mode
After cooling or drying operation stops, the fan runs at high speed to help dry the heat exchanger. The cycle can be set to 30 or 60 minutes; results vary with room temperature and humidity.
High Power Fan Speed Mode
At start-up, increased fan speed supports faster cooling for up to 15 minutes after the first Thermo-ON operation. This mode increases power consumption and sound pressure, and is unavailable at the 125 Pa setting.
Reduced noise on smaller models
Compared with the catalogue’s previous PEY-P JAG models, high-speed sound pressure is reduced by 3 dB on ZM18, 2 dB on ZM24 and 1 dB on ZM30. Installation and inlet selection also affect room noise.
R32 inverter performance
Rated T1 cooling capacities span 5.31–13.20 kW. The UAE table also publishes cooling capacity, input power and efficiency at T3 conditions, with an outdoor temperature of 46°C.
Optional drain pump
The catalogue lists the drain pump as an optional accessory for the PEY-ZM JAG range. Plan condensate drainage and confirm the appropriate accessory with the installer.
Controls for your installation
On/off operation timing and automatic restart are listed for the range. Compatible wall, central and group controls are optional; the illustrated wireless controller requires a separate signal receiver.
Service support
Self-diagnosis with check-code display and failure recall assist servicing. Design access to the concealed unit into the ceiling layout so inspection and maintenance remain practical.
Matched outdoor units
The range pairs with SUY-ZM18/24/30 and PUY-ZM36/45 outdoor units. ZM45 has single- and three-phase choices. The catalogue lists an 18–52°C outdoor operating range and Blue Fin outdoor heat-exchanger coating.
THE DETAILS AT A GLANCE
Specifications.
Compare the five UAE (-AE) PEY-ZM JAG indoor models and their matching outdoor units. Separate 45-class columns show the single-phase and three-phase options.
Scroll across to compare all models, or select one above.
PEY Series — UAE (-AE) R32 ceiling-concealed system specifications
Specification
PEY-ZM18JAG-AE
PEY-ZM24JAG-AE
PEY-ZM30JAG-AE
PEY-ZM36JAG-AE
PEY-ZM45JAG-AE · 1 phase
PEY-ZM45JAG-AE · 3 phase
System combinations & electrical supply
Indoor unit
PEY-ZM18JAG-AE
PEY-ZM24JAG-AE
PEY-ZM30JAG-AE
PEY-ZM36JAG-AE
PEY-ZM45JAG-AE
PEY-ZM45JAG-AE
Paired outdoor unit
SUY-ZM18VA-AE
SUY-ZM24VA-AE
SUY-ZM30VA-AE
PUY-ZM36VKA-AE
PUY-ZM45VKA-AE
PUY-ZM45YKA-AE
Outdoor power supplyV / phase / Hz
220–240 / Single / 50
220–240 / Single / 50
220–240 / Single / 50
220–240 / Single / 50
220–240 / Single / 50
380–415 / Three / 50
Refrigerant
R32
R32
R32
R32
R32
R32
Operation
Cooling Only
Cooling Only
Cooling Only
Cooling Only
Cooling Only
Cooling Only
Operating current — UAE (-AE)A
6.4
8.8
10.9
13.6
16.7
6.3
T1 cooling performance
Rated capacitykW
5.31
7.10
8.80
10.60
13.20
13.20
Capacity — minimum / maximumkW
2.80 / 5.40
3.60 / 8.90
4.10 / 9.70
4.10 / 10.70
6.20 / 15.00
6.20 / 15.00
Rated capacityBtu/h
18,100
24,200
30,000
36,200
45,000
45,000
Capacity — minimum / maximum (as printed)Btu/h
9,554 / 18,425
12,283 / 30,367
13,989 / 33,096
13,989 / 36,598†
21,154 / 40,944†
21,154 / 40,944†
Total inputkW
1.387
1.936
2.400
2.979
3.704
3.704
EERBtu/h/W
13.05
12.50
12.50
12.15
12.15
12.15
T3 cooling performance
Rated capacitykW
4.77
6.39
7.90
9.55
11.90
11.90
Rated capacityBtu/h
16,300
21,800
27,000
32,600
40,600
40,600
Total inputkW
1.772
2.370
3.000
3.544
4.511
4.511
EERBtu/h/W
9.20
9.20
9.00
9.20
9.00
9.00
Indoor unit
Rated power inputkW
0.09
0.14
0.19
0.32
0.32
0.32
Rated running currentA
0.69
0.95
1.25
1.98
1.98
1.98
Dimensions — H × W × Dmm
250 × 900 × 732
250 × 1100 × 732
250 × 1400 × 732
250 × 1400 × 732
250 × 1400 × 732
250 × 1400 × 732
Net weightkg
26.0
29.5
36.5
38.0
38.0
38.0
Air volume — low / medium / highm³/min
12.0 / 14.5 / 17.0
17.5 / 21.0 / 25.0
24.0 / 29.0 / 34.0
29.5 / 35.5 / 42.0
29.5 / 35.5 / 42.0
29.5 / 35.5 / 42.0
External static pressure — table ratingPa
50
50
50
50
50
50
External static pressure — selectablePa
35 / 50 / 70 / 100 / 125
35 / 50 / 70 / 100 / 125
35 / 50 / 70 / 100 / 125
35 / 50 / 70 / 100 / 125
35 / 50 / 70 / 100 / 125
35 / 50 / 70 / 100 / 125
Sound pressure — low / medium / highdB(A)
28 / 32 / 36
29 / 33 / 37
33 / 37 / 41
36 / 40 / 44
36 / 40 / 44
36 / 40 / 44
Outdoor unit
Dimensions — H × W × Dmm
714 × 800 × 285
880 × 840 × 330
880 × 840 × 330
981 × 1050 × 330
1338 × 1050 × 330
1338 × 1050 × 330
Net weightkg
38
48
46
65
100
102
Air volumem³/min
45.6
63.4
63.4
87
116
116
Sound pressuredB(A)
51
54
54
54
55
55
Breaker sizeA
16
20
20
25
40
25
Piping & operating conditions
Pipe diameter — liquid / gasinch
1/4 / 1/2
3/8 / 5/8
3/8 / 5/8
3/8 / 5/8
3/8 / 5/8
3/8 / 5/8
Maximum piping lengthm
30
30
50
50
55
55
Maximum height differencem
20
25
30
30
30
30
Guaranteed outdoor operating range°C
18–52
18–52
18–52
18–52
18–52
18–52
USEFUL INFORMATION
Downloads
Manufacturer reference brochures, ready to explore in more detail.
Confirm the exact model, optional accessories and installation requirements with our team.
A LITTLE MORE GUIDANCE
Frequently asked questions.
Helpful answers for your next commercial project.
Which PEY models are included?+
This page covers PEY-ZM18JAG-AE, PEY-ZM24JAG-AE, PEY-ZM30JAG-AE, PEY-ZM36JAG-AE and PEY-ZM45JAG-AE, with rated T1 cooling capacities from 5.31 to 13.20 kW. The separate 60-class GAG models are not included.
Will the unit fit in a 250 mm ceiling space?+
The indoor unit is 250 mm high, but the complete installation needs additional space for suspension, ductwork, drainage and servicing. Your installer should assess the ceiling void and required access.
Which static-pressure settings are available?+
The JAG range offers 35, 50, 70, 100 and 125 Pa. The installer selects a setting based on airflow and duct resistance. The 150 Pa option shown elsewhere in the catalogue applies to the 60-class GAG model, not this range.
What does Internal Dry Mode do?+
It continues fan operation at high speed for a selected 30 or 60 minutes after cooling or drying stops, helping dry condensation on the heat exchanger. Results depend on indoor temperature and humidity.
When can High Power Fan Speed Mode be used?+
The mode increases fan speed at start-up for a maximum of 15 minutes after the first Thermo-ON operation. It raises power consumption and sound pressure and cannot be used when external static pressure is set to 125 Pa.
Is the drain pump supplied as standard?+
No. The catalogue’s PEY function table marks the drain pump as optional. Confirm the drainage arrangement and suitable accessory during installation planning.
Is there a three-phase option?+
Yes. PEY-ZM45JAG-AE can be paired with the PUY-ZM45YKA-AE three-phase outdoor unit. The specification selector also includes the single-phase PUY-ZM45VKA-AE option.