Comfort at your preferred pace.
Four fan speeds, an automatic setting and five vane positions make it easier to choose how the air reaches you. Swing operation adds another airflow option.


Recreated product and application images are illustrative. Appearance and accessories vary by model.
CITY MULTI · WALL-MOUNTED UNIT
1.2–5.6 kW nominal cooling capacity
A compact wall-mounted range with a simple white design, four fan speeds plus Auto, and adjustable vane angles for individual rooms.
COMFORT IN THE RIGHT FORM
A compact wall-mounted range with a simple white design, four fan speeds plus Auto, and adjustable vane angles for individual rooms.

WALL-MOUNTED UNIT
The white, square-edged body sits comfortably alongside the straight lines of walls and ceilings. The P10–P32 models are 773 mm wide, while P40/P50 models are 898 mm wide.
Four fan speeds, an automatic setting and five vane positions make it easier to choose how the air reaches you. Swing operation adds another airflow option.
Selected low-capacity models have a published low-speed sound pressure of 22 dB(A). An optional external LEV box and drain-pump kit can be considered as part of the installation design.
COMFORT IN THE DETAILS
Explore the features and available options of the PKFY-P VLM-E range.
Seven capacity classes span 1.2 to 5.6 kW of nominal cooling for individual room requirements.
Choose a fixed airflow speed or automatic fan adjustment to suit the room conditions.
Five selectable vane positions and swing operation help tailor air direction.
Improvements to the unit structure and line-flow fan reduce noise compared with the predecessor ranges cited in the catalogue. Actual sound depends on model and speed.
The PAC-SK01DM-E drain-pump kit provides additional freedom in drain routing and is listed for P10–P50.
PAC-SK17LE-E is listed for P10; PAC-SG95LE-E is listed for P15–P50. Select the accessory for the exact model.
Accessories and compatible controllers are selected separately. Availability and supported combinations depend on the exact model.
THE DETAILS, MODEL BY MODEL
Compare capacities, dimensions and operating data from the September 2026 City Multi catalogue.
| Indoor model | PKFY-P10VLM-E |
|---|---|
| Nominal cooling capacity | 1.2 kW |
| Nominal heating capacity | 1.4 kW |
| Power supply | 1-phase 220–240 V, 50 Hz / 220–230 V, 60 Hz |
| Indoor power input — cooling | 0.02 kW |
| Indoor power input — heating | 0.01 kW |
| Current — cooling | 0.2 A |
| Current — heating | 0.15 A |
| Unit dimensions H × W × D | 299 × 773 × 237 mm |
| Unit net weight | 11 kg |
| Fan motor | DC motor |
| Airflow (Low / Mid2 / Mid1 / High) | 3.3 / 3.5 / 3.8 / 4.2 m³/min |
| Sound pressure (Low / Mid2 / Mid1 / High) | 22 / 24 / 26 / 28 dB(A) |
| External static pressure | 0 Pa |
| Air filter | PP honeycomb |
| Refrigerant liquid pipe (flare) | 6.35 mm |
| Refrigerant gas pipe (flare) | 12.7 mm |
| Drain connection | I.D. 16 mm |
Nominal cooling conditions: 27°C DB / 19°C WB indoors and 35°C DB outdoors. Nominal heating conditions: 20°C DB indoors and 7°C DB / 6°C WB outdoors. Where stated in the catalogue, ratings use 7.5 m of piping and no level difference. DB means dry bulb; WB means wet bulb.
Power input is for the indoor unit, not the complete system. Heating requires a compatible heating-capable outdoor system. Sound figures are measured in an anechoic room; actual levels depend on the installation. Ducted-unit performance is stated at the factory pressure setting. Our team can help confirm selection conditions and installation requirements for your project.
| Model | Cooling (kW) | Heating (kW) | H × W × D (mm) | Weight (kg) |
|---|---|---|---|---|
| 1.2 | 1.4 | 299 × 773 × 237 | 11 | |
| 1.7 | 1.9 | 299 × 773 × 237 | 11 | |
| 2.2 | 2.5 | 299 × 773 × 237 | 11 | |
| 2.8 | 3.2 | 299 × 773 × 237 | 11 | |
| 3.6 | 4 | 299 × 773 × 237 | 11 | |
| 4.5 | 5 | 299 × 898 × 237 | 13 | |
| 5.6 | 6.3 | 299 × 898 × 237 | 13 |