Air distribution to suit the project.
The catalogue includes duct, plenum and rear-suction arrangements, depending on model and accessories. Select the airflow configuration together with the required capacity and static pressure.


Recreated product and application images are illustrative. Appearance and accessories vary by model.
CITY MULTI · LARGE-CAPACITY FLOOR-STANDING UNIT
22.4–56.0 kW nominal cooling capacity
A floor-standing range for larger occupied spaces, with four nominal cooling capacities and model-specific airflow, duct and plenum options.
COMFORT IN THE RIGHT FORM
A floor-standing range for larger occupied spaces, with four nominal cooling capacities and model-specific airflow, duct and plenum options.

LARGE-CAPACITY FLOOR-STANDING UNIT
Four YM-E models span 22.4 to 56.0 kW of nominal cooling. A floor-standing format offers a practical option for larger halls and other open occupied spaces.
The catalogue includes duct, plenum and rear-suction arrangements, depending on model and accessories. Select the airflow configuration together with the required capacity and static pressure.
Suitable City Multi combinations can serve larger shared areas alongside individually conditioned rooms. Outdoor-unit compatibility and connected-capacity limits must be checked for the chosen configuration.
COMFORT IN THE DETAILS
Explore the features and available options of the PFFY-P YM-E range.
P200, P250, P400 and P500 offer 22.4, 28.0, 45.0 and 56.0 kW nominal cooling capacity. The separate YMH-E models are not part of this page.
P200/P250 provide high and low airflow. P400/P500 use high airflow with belt-driven fans; performance differs between 50 and 60 Hz.
The catalogue lists outside-air duct flanges for all four capacities and a plenum accessory for P400/P500.
Applicable options allow airflow and static pressure to be matched to project requirements. Confirm the configuration against the technical data.
The range uses a three-phase, four-wire 380–400–415 V power supply at 50/60 Hz.
The floor-standing arrangement places the equipment at an accessible level. Allow the clearances needed for airflow, connections and maintenance.
Accessories and compatible controllers are selected separately. Availability and supported combinations depend on the exact model.
THE DETAILS, MODEL BY MODEL
Compare capacities, dimensions and operating data from the September 2026 City Multi catalogue.
| Indoor model | PFFY-P200YM-E |
|---|---|
| Nominal cooling capacity | 22.4 kW |
| Nominal heating capacity | 25 kW |
| Power supply | 3-phase, 4-wire 380–400–415 V, 50/60 Hz |
| Indoor power input — cooling (50 / 60 Hz) | 0.490 / 0.680 kW |
| Indoor power input — heating (50 / 60 Hz) | 0.490 / 0.680 kW |
| Current — cooling (380 / 400 / 415 V; 50 Hz then 60 Hz) | 0.97–0.98–0.99 / 1.24–1.23–1.22 A |
| Current — heating (380 / 400 / 415 V; 50 Hz then 60 Hz) | 0.97–0.98–0.99 / 1.24–1.23–1.22 A |
| Unit dimensions H × W × D | 1,665 × 1,200 × 500 mm |
| Unit net weight | 157 kg |
| Fan motor | 3-phase induction motor |
| Airflow (High–Low at 50 Hz / High–Low at 60 Hz) | 65–59 / 69–60 m³/min |
| Sound pressure (High–Low at 50 Hz / High–Low at 60 Hz) | 58–56 / 60–56 dB(A) |
| External static pressure (50 / 60 Hz) | 0 / 0 Pa |
| Air filter | PP honeycomb fabric |
| Refrigerant liquid pipe (brazed) | 9.52 mm |
| Refrigerant gas pipe (brazed) | 22.22 mm |
| Drain connection | Rc 1 inch |
Nominal cooling conditions: 27°C DB / 19°C WB indoors and 35°C DB outdoors. Nominal heating conditions: 20°C DB indoors and 7°C DB / 6°C WB outdoors. Where stated in the catalogue, ratings use 7.5 m of piping and no level difference. DB means dry bulb; WB means wet bulb.
Power input is for the indoor unit, not the complete system. Heating requires a compatible heating-capable outdoor system. Sound figures are measured in an anechoic room; actual levels depend on the installation. Ducted-unit performance is stated at the factory pressure setting. Electrical input, static pressure and sound values separated by a slash are for 50 Hz / 60 Hz; pressure and sound are stated at 380 V. Our team can help confirm selection conditions and installation requirements for your project.
| Model | Cooling (kW) | Heating (kW) | H × W × D (mm) | Weight (kg) |
|---|---|---|---|---|
| 22.4 | 25 | 1,665 × 1,200 × 500 | 157 | |
| 28 | 31.5 | 1,665 × 1,200 × 500 | 158 | |
| 45 | 50 | 1,800 × 1,860 × 650 | 310 | |
| 56 | 63 | 1,800 × 1,860 × 650 | 362 |