A quieter approach to comfort.
The centrifugal fan and coil are designed to limit operating noise. Low-speed sound pressure starts at 22 dB(A) on P15 under the catalogue’s test conditions.


Recreated product and application images are illustrative. Appearance and accessories vary by model.
CITY MULTI · LOW STATIC PRESSURE DUCTED UNIT
1.7–7.1 kW nominal cooling capacity
A 200 mm-high concealed indoor unit with low-noise operation, three fan speeds and a choice of models with or without a drain pump.
COMFORT IN THE RIGHT FORM
A 200 mm-high concealed indoor unit with low-noise operation, three fan speeds and a choice of models with or without a drain pump.

LOW STATIC PRESSURE DUCTED UNIT
The slim 200 mm unit can fit into restricted ceiling voids. The indoor unit stays concealed, leaving only the selected air grilles visible in the finished room.
The centrifugal fan and coil are designed to limit operating noise. Low-speed sound pressure starts at 22 dB(A) on P15 under the catalogue’s test conditions.
VMS1 models include a drain pump with lift up to 550 mm. VMS1L models omit the pump, offering an alternative for installations where low-noise operation and a suitable gravity drain are priorities.
COMFORT IN THE DETAILS
Explore the features and available options of the PEFY-P VMS1(L)-E range.
Every model is 200 mm high. Unit widths are 790, 990 or 1,190 mm according to capacity.
Choose 5, 15, 35 or 50 Pa to suit the ductwork. The factory setting is 15 Pa.
Low, medium and high airflow settings allow the installer and user to balance air delivery and sound.
A pump is standard on VMS1 and omitted on VMS1L. An optional drain-pump kit is listed for VMS1L models.
A washable PP honeycomb fabric filter supports routine care. Provide suitable access to the concealed unit for maintenance.
MAC-100FT-E can be installed on the air-inlet side using the required PQ attachment. It is an accessory, not standard equipment.
Accessories and compatible controllers are selected separately. Availability and supported combinations depend on the exact model.
THE DETAILS, MODEL BY MODEL
Compare capacities, dimensions and operating data from the September 2026 City Multi catalogue.
| Indoor model | PEFY-P15VMS1-E |
|---|---|
| Drain-pump variant | VMS1 · built-in drain pump |
| Nominal cooling capacity | 1.7 kW |
| Nominal heating capacity | 1.9 kW |
| Power supply | 1-phase 220–240 V, 50/60 Hz |
| Indoor power input — cooling | 0.05 kW |
| Indoor power input — heating | 0.03 kW |
| Current — cooling | 0.42 A |
| Current — heating | 0.31 A |
| Unit dimensions H × W × D | 200 × 790 × 700 mm |
| Unit net weight | 19 kg |
| Fan motor | DC motor |
| Airflow (Low / Mid / High) | 5 / 6 / 7 m³/min |
| Sound pressure (Low / Mid / High) | 22 / 24 / 28 dB(A) |
| External static pressure | 5 / 15 / 35 / 50 (factory: 15) Pa |
| Air filter | PP honeycomb fabric (washable) |
| Refrigerant liquid pipe (brazed) | 6.35 mm |
| Refrigerant gas pipe (brazed) | 12.7 mm |
| Drain connection | O.D. 32 mm |
Nominal cooling conditions: 27°C DB / 19°C WB indoors and 35°C DB outdoors. Nominal heating conditions: 20°C DB indoors and 7°C DB / 6°C WB outdoors. Where stated in the catalogue, ratings use 7.5 m of piping and no level difference. DB means dry bulb; WB means wet bulb.
Power input is for the indoor unit, not the complete system. Heating requires a compatible heating-capable outdoor system. Sound figures are measured in an anechoic room; actual levels depend on the installation. Ducted-unit performance is stated at the factory pressure setting. Our team can help confirm selection conditions and installation requirements for your project.
| Model | Cooling (kW) | Heating (kW) | H × W × D (mm) | Weight (kg) |
|---|---|---|---|---|
| 1.7 | 1.9 | 200 × 790 × 700 | 19 | |
| 2.2 | 2.5 | 200 × 790 × 700 | 19 | |
| 2.8 | 3.2 | 200 × 790 × 700 | 20 | |
| 3.6 | 4 | 200 × 790 × 700 | 20 | |
| 4.5 | 5 | 200 × 990 × 700 | 24 | |
| 5.6 | 6.3 | 200 × 990 × 700 | 24 | |
| 7.1 | 8 | 200 × 1,190 × 700 | 28 |