Control the air arriving indoors.
Outlet-air temperature control helps temper the incoming air. Delivered temperature can still vary with outdoor conditions, system operation and protective functions.


Recreated product and application images are illustrative. Appearance and accessories vary by model.
CITY MULTI · FRESH AIR INTAKE UNIT
14.0–28.0 kW nominal cooling capacity
A dedicated fresh-air unit that pre-treats outside air before supplying it to the room, with selectable airflow modes and static pressure up to 250 Pa.
COMFORT IN THE RIGHT FORM
A dedicated fresh-air unit that pre-treats outside air before supplying it to the room, with selectable airflow modes and static pressure up to 250 Pa.

FRESH AIR INTAKE UNIT
The VMHS-E-F range treats incoming outdoor air before it reaches the occupied space. It is designed for the fresh-air load; separate room units handle the internal thermal load.
Outlet-air temperature control helps temper the incoming air. Delivered temperature can still vary with outdoor conditions, system operation and protective functions.
Normal- and high-airflow modes each provide three fan settings. Four external static-pressure settings help match the unit to the fresh-air ductwork.
COMFORT IN THE DETAILS
Explore the features and available options of the PEFY-P VMHS-E-F range.
Provides temperature-controlled fresh-air intake for a zone. This unit is not intended to carry the room’s internal cooling or heating load.
Normal and high airflow each have low, medium and high settings. The model table shows both sets of airflow and sound figures.
Select 100, 150, 200 or 250 Pa, with 200 Pa as the factory setting. Airflow must remain within the manufacturer’s usable range.
A DC fan motor operates from a single-phase 220–230–240 V supply at 50/60 Hz.
A model-specific pump kit provides lift up to 700 mm for more flexibility in drain routing.
An air filter must be fitted on the intake side. The catalogue lists optional long-life filters and filter boxes; access is required for maintenance.
Accessories and compatible controllers are selected separately. Availability and supported combinations depend on the exact model.
THE DETAILS, MODEL BY MODEL
Compare capacities, dimensions and operating data from the September 2026 City Multi catalogue.
| Indoor model | PEFY-P125VMHS-E-F |
|---|---|
| Nominal cooling capacity | 14 kW |
| Nominal heating capacity | 8.9 kW |
| Power supply | 1-phase 220–230–240 V, 50/60 Hz |
| Indoor power input — cooling | 0.22 kW |
| Indoor power input — heating | 0.23 kW |
| Current — cooling (220 V) | 1.43 A |
| Current — heating (220 V) | 1.52 A |
| Unit dimensions H × W × D | 380 × 1,195 × 900 mm |
| Unit net weight | 49 kg |
| Fan motor | DC motor |
| Airflow (Low / Mid / High; normal-airflow mode) | 14 / 15.5 / 18 m³/min |
| Sound pressure (Low / Mid / High; normal-airflow mode) | 34 / 37 / 41 dB(A) |
| Airflow — high-airflow mode (Low / Mid / High) | 15.5 / 18 / 20 m³/min |
| Sound — high-airflow mode (Low / Mid / High) | 36 / 40 / 42 dB(A) |
| External static pressure | 100 / 150 / 200 / 250 (factory: 200) Pa |
| Air filter | Optional long-life filter; intake filtration required |
| Refrigerant liquid pipe (brazed) | 9.52 mm |
| Refrigerant gas pipe (brazed) | 15.88 mm |
| Drain connection | O.D. 32 mm |
| Cooling intake-temperature range | 17°C DB / 15.5°C WB to 43°C DB / 35°C WB |
| Heating intake-temperature range | −10°C DB to 20°C DB |
Fresh-air ratings use different conditions from room units: cooling at 33°C DB / 28°C WB intake and 33°C DB outdoors, with an 18°C controller setting; heating at 0°C DB / −2.9°C WB intake and outdoors, with a 25°C controller setting. These capacities are for pre-treating outside air, not the room’s internal thermal load. DB means dry bulb; WB means wet bulb.
Power input is for the indoor unit, not the complete system. Heating requires a compatible heating-capable outdoor system. Sound figures are measured in an anechoic room; actual levels depend on the installation. Ducted-unit performance is stated at the factory pressure setting. Our team can help confirm selection conditions and installation requirements for your project.
For P250, the medium fan setting at 100 Pa differs from the tabulated airflow; refer to the manufacturer’s fan curves. Outdoor-unit compatibility and fresh-air connection limits apply.
| Model | Cooling (kW) | Heating (kW) | H × W × D (mm) | Weight (kg) |
|---|---|---|---|---|
| 14 | 8.9 | 380 × 1,195 × 900 | 49 | |
| 22.4 | 13.9 | 470 × 1,250 × 1,120 | 78 | |
| 28 | 17.4 | 470 × 1,250 × 1,120 | 81 |
KEEP THE DETAILS CLOSE
Open the original product information and specification tables, or browse the complete City Multi catalogue.
YOUR PROJECT, CONSIDERED
Our team can help you confirm capacity, outdoor-unit compatibility, controls and installation requirements.