A range for different scales.
Models span 4.5 to 28.0 kW of nominal cooling. The P40–P140 unit is 380 mm high; P160–P250 models use a larger 470 mm-high unit.


Recreated product and application images are illustrative. Appearance and accessories vary by model.
CITY MULTI · HIGH STATIC PRESSURE DUCTED UNIT
4.5–28.0 kW nominal cooling capacity
A concealed ducted range for longer air paths and larger spaces, with model-dependent static pressure up to 250 Pa and optional drain-pump and filtration accessories.
COMFORT IN THE RIGHT FORM
A concealed ducted range for longer air paths and larger spaces, with model-dependent static pressure up to 250 Pa and optional drain-pump and filtration accessories.

HIGH STATIC PRESSURE DUCTED UNIT
Higher external static pressure gives designers more flexibility for duct routing and air distribution. Choose a capacity and pressure setting that match the resistance of the planned duct system.
Models span 4.5 to 28.0 kW of nominal cooling. The P40–P140 unit is 380 mm high; P160–P250 models use a larger 470 mm-high unit.
Optional drain pumps offer lift up to 550 mm on P40–P140 or 700 mm on P160–P250. A long-life filter and matching filter box are also available and should be accessible for servicing.
COMFORT IN THE DETAILS
Explore the features and available options of the PEFY-P VMHS-E range.
P40–P140 offer settings from 50 to 200 Pa. P160/P180 offer 100 to 250 Pa, while P200/P250 offer 50 to 250 Pa.
Low, medium and high fan speeds provide a choice of airflow within the selected model’s operating envelope.
The range uses DC fan motors. Airflow and electrical input depend on capacity and the selected pressure setting.
Choose the correct pump kit for the model and required lift. Pumps are optional rather than built into the standard unit.
The catalogue recommends a synthetic-fibre long-life filter and a matching filter box, both selected by model size.
The unit connects to field-installed ductwork. Allow ceiling space for the unit, insulation, connections and service access.
Accessories and compatible controllers are selected separately. Availability and supported combinations depend on the exact model.
THE DETAILS, MODEL BY MODEL
Compare capacities, dimensions and operating data from the September 2026 City Multi catalogue.
| Indoor model | PEFY-P40VMHS-E |
|---|---|
| Nominal cooling capacity | 4.5 kW |
| Nominal heating capacity | 5 kW |
| Power supply | 1-phase 220–230–240 V, 50/60 Hz |
| Indoor power input — cooling | 0.055 kW |
| Indoor power input — heating | 0.055 kW |
| Current — cooling (220 / 230 / 240 V) | 0.41 / 0.39 / 0.38 A |
| Current — heating (220 / 230 / 240 V) | 0.41 / 0.39 / 0.38 A |
| Unit dimensions H × W × D | 380 × 745 × 900 mm |
| Unit net weight | 35 kg |
| Fan motor | DC motor |
| Airflow (Low / Mid / High) | 10 / 12 / 14 m³/min |
| Sound pressure (Low / Mid / High) | 20 / 23 / 27 dB(A) |
| External static pressure | 50 / 100 / 150 / 200 (factory: 50) Pa |
| Air filter | Optional long-life filter and filter box |
| Refrigerant liquid pipe (brazed) | 6.35 mm |
| Refrigerant gas pipe (brazed) | 12.7 mm |
| Drain connection | O.D. 32 mm |
Nominal cooling conditions: 27°C DB / 19°C WB indoors and 35°C DB outdoors. Nominal heating conditions: 20°C DB indoors and 7°C DB / 6°C WB outdoors. Where stated in the catalogue, ratings use 7.5 m of piping and no level difference. DB means dry bulb; WB means wet bulb.
Power input is for the indoor unit, not the complete system. Heating requires a compatible heating-capable outdoor system. Sound figures are measured in an anechoic room; actual levels depend on the installation. Ducted-unit performance is stated at the factory pressure setting. Our team can help confirm selection conditions and installation requirements for your project.
| Model | Cooling (kW) | Heating (kW) | H × W × D (mm) | Weight (kg) |
|---|---|---|---|---|
| 4.5 | 5 | 380 × 745 × 900 | 35 | |
| 5.6 | 6.3 | 380 × 745 × 900 | 35 | |
| 7.1 | 8 | 380 × 745 × 900 | 35 | |
| 8 | 9 | 380 × 1,030 × 900 | 45 | |
| 9 | 10 | 380 × 1,030 × 900 | 45 | |
| 11.2 | 12.5 | 380 × 1,195 × 900 | 51 | |
| 14 | 16 | 380 × 1,195 × 900 | 51 | |
| 16 | 18 | 380 × 1,195 × 900 | 53 | |
| 18 | 20 | 470 × 1,250 × 1,120 | 84 | |
| 20.2 | 22.5 | 470 × 1,250 × 1,120 | 84 | |
| 22.4 | 25 | 470 × 1,250 × 1,120 | 97 | |
| 28 | 31.5 | 470 × 1,250 × 1,120 | 100 |
KEEP THE DETAILS CLOSE
Open the original product information and specification tables, or browse the complete City Multi catalogue.
YOUR PROJECT, CONSIDERED
Our team can help you confirm capacity, outdoor-unit compatibility, controls and installation requirements.